In today’s society, with the vigorous development of the electric vehicle industry and the popularization of the concept of green travel, the importance of charging stations as key infrastructure for electric vehicle energy replenishment has become increasingly prominent. However, along with the opportunities come the safety risks and challenges that cannot be ignored in the operation of charging stations. From electrical safety, and fire safety to personal safety, every link affects the nerves of users, operators, and even the entire society.
This article summarizes the typical problems of common safety hazards in charging stations, hoping to be of some help to the station operators.
Key safety hazards and typical problems
The shell of the AC and DC charging pile body is not grounded.
It does not meet the requirement that “the metal shell of the charging equipment and the metal components such as the bracket and the base should be reliably connected to the grounding device of the building nearby”.
Suggestion: The metal shell of the charging equipment and the metal components such as the bracket and the base should be reliably connected to the grounding device of the building nearby or set up an independent grounding electrode, and the grounding resistance should be no more than 4Ω.

The metal shell of the distribution box is not grounded.
It does not meet the requirement that “the following metal parts of the power facilities should be reliably grounded through the protective grounding device”.
Suggestion: The outer shell of the distribution box should be reliably connected to the grounding device of the building nearby (or connected to the independent grounding device of the site), and the grounding resistance should be no more than 4Ω.
The site selection of some charging stations failed to meet the fire safety standards.
High-power charging facilities (such as DC charging piles and charging host systems) were installed on the underground floor of the building. This layout violates the relevant provisions of the “Electric Vehicle Distributed Charging Facilities Engineering Technical Standards”.
Suggestion: High-power charging facilities (such as non-on-board chargers and charging host systems) should be avoided on the underground floor of the building, but are more suitable for a centralized layout in a certain area on the ground of the building. When selecting the location of the charging station, full consideration should be given to fire safety requirements, ensuring that the selected location meets the relevant fire protection standards, and is equipped with necessary fire-fighting facilities to ensure the safety of personnel and property.
Some charging stations are not equipped with fire extinguishers
- It does not meet the current standards of the “Building Fire Extinguisher Configuration Design Specifications”. Specifically for the configuration of fire extinguishers in outdoor charging areas, there are the following requirements:
- If plug-in hybrid vehicles are not considered to enter, the charging station should be equipped with fire extinguishers at the light hazard level; if plug-in hybrid vehicles are considered to enter, the charging station needs to be equipped with fire extinguishers at the severe hazard level.
In response to the above problems, we put forward the following improvement suggestions:
- Ensure that the fire-fighting equipment in the charging station is fully equipped and in good condition.
- For charging facility areas where no plug-in hybrid vehicles enter, it is recommended to configure portable dry powder fire extinguishers of no less than 4 kg. The placement distance of each fire extinguisher should be 15 meters. If the distance is less than 15 meters, it needs to be placed in the rounded position, and ensure that each configuration point is equipped with at least 2 fire extinguishers.
- For charging facility areas where plug-in hybrid vehicles enter, it is recommended to also configure portable dry powder fire extinguishers of no less than 4 kg, but the placement distance of each fire extinguisher should be shortened to 9 meters. If the distance is less than 9 meters, it needs to be placed in the rounded position, and ensure that each configuration point is equipped with at least 2 fire extinguishers.
- In addition, it is recommended to add cart-type water-based fire extinguishers or cart-type water spray fire extinguishers with a fire extinguishing agent filling volume of not less than 30 liters near the charging and swapping infrastructure. The maximum protection distance of these cart-type fire extinguishers can reach 30 meters to provide more comprehensive fire safety protection.

A large amount of flammable cardboard and debris are currently piled up in the charging station, which constitutes an extremely serious fire safety hazard.
It does not meet the requirements of the “Urban Public Facilities Electric Vehicle Charging and Swapping Facility Operation and Management Service Specifications”, which clearly states: “It is strictly prohibited to store flammable and explosive items, polluting and corrosive media in the working area of charging and swapping facilities.”
Recommendations:
- Immediately organize forces to thoroughly clean up all flammable debris accumulated in the charging station.
- Strengthen the fire safety management of the station to ensure that all rules and regulations are strictly implemented.
- Reasonably plan the station space, implement effective isolation measures, strictly separate the express accumulation area from the charging area, and avoid any possible safety risks.
Some charging piles are improperly set up at the door of the evacuation passage and arranged close to the windows of the building.
If a fire occurs during the charging process, this layout will greatly hinder the safe evacuation of personnel and constitute a significant fire safety hazard.
In response to this problem, the following improvement measures are recommended:
- Immediately adjust the layout of charging equipment to ensure that they are not located on both sides of the evacuation passage or at the door to avoid obstruction to emergency evacuation.
- Implement effective isolation measures to clearly separate the charging area from both sides of the evacuation passage to ensure that personnel can evacuate quickly and unimpeded in an emergency.
The input cable of the charging pile is not firmly connected.
Among the after-sales problems of the charging pile, the most common problem is that the contact area between the cable and the circuit breaker is not enough or the screws are not tightened. The consequence of this problem is that the circuit breaker is locally heated, causing the circuit breaker to burn, and the local severe heating inside the charging pile causes derating. In severe cases, it may cause a fire.
Suggestion: When looking for a professional to install, you can remember the installation problem of the charging pile input cable.
Typical problems with major safety hazards
The outlet switch of the low-voltage cabinet of the box transformer is not a leakage switch).
It does not meet the requirement that “flame-retardant cables and cable protection tubes should be used for the power supply line, and air switches with leakage protection functions should be installed.” The switch will not trip immediately when a person is electrocuted, and there is a major safety hazard of electric shock.
Suggestion: One side of the low-voltage cabinet, distribution box outlet switch, or charging pile AC incoming switch should have a leakage protection function.

When leakage occurs, the switch cannot be cut off in the shortest time, which may not play an effective protective role.
Suggestion: The residual current protection device (RCD) action test should be performed at least once a month, and the action characteristic test under residual current conditions should be performed at least once a year. The leakage action current value of the leakage protection switch of the charging pile should be set to 100mA or less, and the leakage action time should be set to the minimum time.

The distribution box is not equipped with a surge protector, and the charging pile is not equipped inside, or the surge protector in the distribution box and the charging pile has failed.
It does not meet the requirement of “When the charging equipment must take lightning protection measures, a surge protection device should be installed between the conductor and PE”.
Suggestion: Install or replace the faulty surge protector in time.
The holes for the cable inlet and outlet in the distribution box are not blocked.
If not blocked, small animals may enter and cause short circuit faults; it will also cause severe condensation in the distribution box, with more water droplets, causing oxidation and rusting of electrical equipment, or causing serious moisture and corrosion at electrical connection points such as copper bars and cables in the distribution box.
Suggestion: The holes in the distribution box should be tightly blocked with flame-retardant fireproof mud.
The air pressure of the SF6 ring network cabinet in the high-voltage room of the box transformer is low (it is close to the red low-pressure area or is in the red low-pressure area), which affects the safe operation of the high-voltage cabinet.
Suggestion: Entrust a qualified power construction company to find out the cause as soon as possible and repair or replace the equipment.

The problem of connecting the large switch to the small wire in the low-voltage outlet cabinet of the box transformer:
At present, there is an improper wiring method, that is, the switch with a rated current of 63A/250A is mistakenly connected to the lighting or monitoring cables of 2.5mm2 and 1.5mm2. This mismatched configuration causes the switch to fail to trip effectively when the cable fails (such as accidentally dug or burned by construction workers), and thus cannot play the due protective role.
Suggestion:
- According to the actual load requirements, the specifications of the switch and cable should be reasonably configured to ensure that each switch corresponds to an independent outlet circuit to avoid overload and short circuit risks.
- Strengthen regular inspections during equipment operation, especially infrared temperature measurement inspections, to timely discover and deal with potential safety hazards.
Irregular grounding of distribution boxes and charging piles:
The grounding system of distribution boxes and charging piles is irregular, which is manifested in the insufficient welding contact area between the grounding flat iron and the equipment base. This irregular grounding method may reduce the reliability and effectiveness of grounding, thereby affecting the safe operation of the equipment.
Suggestions: Carry out a comprehensive inspection of the grounding system to ensure that the welding contact area between the grounding flat iron and the equipment base meets the standard requirements to improve the reliability and stability of grounding.
The insulating gloves and insulating shoes are seriously aged and damaged and have not been sent to professional testing institutions for regular inspection.
There is a lack of insulating safety tools such as test rods and grounding wires.
It does not meet the requirements of the “Electric Power Safety Work Regulations (Electrical Part of Power Plants and Substations)”. Insulating safety tools can only be used after passing the test and shall not be used beyond the expiration date.
Suggestions:
- Insulated safety tools should be fully equipped and in good condition;
- All kinds of safety tools should be tested according to the specified test items, cycles, and requirements. They can only be used after passing the test and shall not be used beyond the expiration date.
The gas pressure of the site fire extinguisher is insufficient, and there is no regular inspection record of the fire extinguisher.
It does not meet the requirements of “configuring fire-fighting facilities and equipment by national standards and industry standards, setting up fire safety signs, and regularly organizing inspections and maintenance to ensure that they are intact and effective”.
Suggestions:
- Timely replacement of expired and invalid fire-fighting facilities and equipment;
- Check and record fire-fighting facilities and equipment every month.
Typical problems of minor safety hazards
- Water ingress into the high-voltage room of the box transformer; water ingress into the charging pile, and a lot of water accumulation inside the equipment.
Suggestions: Check the reasons for water ingress and water seepage in the equipment, and perform maintenance promptly.
- The charging pile gun line is detached, the charging gun head is damaged, the insulation cap is missing, and the gun head locking device is damaged and ineffective.
It does not meet the requirement that “the shell of the power supply plug and the vehicle plug should completely seal the terminal and the end of the charging cable”.
Suggestions:
- Fix the insulation layer of the gun cable to prevent the gun cable from being exposed and cutting the cable;
- Replace or repair the problematic charging gun head in time to avoid accidents such as electric shock and leakage or damage to the vehicle charging.
- There is no safety warning sign or the warning sign is incomplete at the charging pile of the station.
It does not meet the requirement that “electrical equipment should have clear, complete and correct signs and safety warnings, and there should be effective contact information and owner information of daily maintenance personnel. Changes in relevant personnel and information should be replaced in time”.
Suggestions:
- Post various safety warning signs according to the requirements of the regulations.
- Charging equipment should be specially marked with “electricity hazard”, “minors are prohibited from operating”, or “people and vehicles are separated during charging” warning signs and safety precautions in conspicuous locations, and outdoor places should also be specially marked with “no operation in thunderstorm weather” warning signs.
- The station did not post the “illegally modified electric two-wheeled vehicles are prohibited from entering for charging” sign.
Suggestion: Post notices at the stations to strictly prohibit illegally modified electric two-wheelers from entering for charging, and strengthen inspections and supervision within the stations.
The above are suggestions for building charging station safety risks and handling. Customers who need to build stations can use this as a reference.