IP54 Charging Piles Should Be Installed with Film Canopies

Charging piles with an IP54 protection rating should be installed with film canopies if used outdoors, especially DC charging piles. Below, I will explain the meaning of IP54 in the protection rating standard, the test method for IP54, and why IP54 DC charging piles cannot withstand slanting winds and heavy rain.

BLUESKY L1 home charging piles

The Meaning of IP54

The protection rating standard is the “root” standard. The latest version is the 2017 edition, GB/T4208-2017 “Degrees of Protection Provided by Enclosures (IP Code)”, which is equivalent to IEC60529:2013 “Degrees of Protection Provided by Enclosures (IP Code)”.

The first characteristic numeral 5 indicates:
  •  Prevents access to hazardous parts by tools with a diameter of at least 1.0 mm;
  •  Dust ingress is not completely prevented, but the amount of dust entering must not affect the normal operation of the equipment or its safety.
  •  Prevents solid foreign objects with a diameter of at least 1.0 mm from entering the equipment enclosure.
The second characteristic numeral 4 indicates:
  • Prevents the equipment from being adversely affected by water splashing from all directions against the enclosure.

After reading the detailed description in the standard, let’s look at the test requirements in the standard to see how a third-party laboratory conducts the IP54 test.

IP54 Test Method

Dust Test

The standard describes the IP5X dust test as follows.

The test should be conducted in a dustproof chamber. The powder circulation pump within the sealed chamber can be replaced with other methods that can suspend talc powder. The talc powder should be filtered through a metal square-hole sieve. The wire diameter is 50 μm and the mesh size is 75 μm. The amount of talc powder used is 2 kg per cubic meter of chamber volume, and the number of uses should not exceed 20.

What does a metal square-hole sieve look like?

The wire diameter is 50 μm and the mesh size is 75 μm. The sieve produced by the 540th Factory of China Aviation Industry Corporation, used in some authoritative laboratories, is shown in the figure below.

75μm pore size metal sieve

A charging station was placed in a confined space, and 75μm talcum powder was allowed to “fly” around for 8 hours. After standing still, the charging station remained operational when turned on. The specific equipment is shown in Figure 2. A dust collection port and a dust extraction port are located at the bottom of the unit. A high-pressure turbine circulating fan is installed at the dust extraction port, sucking up dust to the top of the inner chamber. The dust is then blown vertically downward from the top. When the dust lands on the sidewalls of the funnel, a vibrating device returns the dust to the dust extraction port, thus repeating the cycle.

Waterproof Test

  • IPX4: Water spraying is performed vertically and at a 180-degree angle on both sides at a rate of 0.07 liters/minute from each nozzle for 10 minutes.
  • IPX5: Water spraying is performed vertically and at a rate of 12.5 liters/minute from a 6.3mm diameter nozzle at a distance of 2.5 to 3 meters for at least 3 minutes.

Handheld test device for protection against water spray and splash

DC charging piles cannot withstand slanting winds and heavy rain.

To achieve IP5X, the common practice is to add dust-proof cotton to the air inlets and outlets. A dust-proof cotton pore size of less than 1mm is sufficient to meet the test requirements. Passing third-party laboratory testing is not difficult. Please refer to the acceptance conditions after IP5X and IPX4 testing.

Some designs use a “zigzag” air duct, where the air outlet does not directly face the charging module, and even include an “intermediate filter” to collect dust. Even if an unprotected charging pile is filled with 75μm talcum powder, it will still work after being turned on. Even if the dust-proof cotton is covered with dust and the air duct is blocked, it will still operate for a while before triggering the overtemperature protection. As long as the louvers are designed at a 45-degree angle, water will not splash into the device.

Charging piles that pass IP54 testing are actually unable to withstand the long-term erosion of slanting winds and heavy rain. Slanting winds and heavy rain carry damp fluff that sticks to the dust-proof cotton at the air duct entrance, easily blocking the air duct. The long-term presence of moisture reduces the safety distance of high-voltage and strong electrical currents. If the air ducts aren’t cleaned immediately after every downpour, the lifespan of an IP54-rated charging station will be significantly reduced.

DC charging stations

Adding a canopy can “reduce maintenance costs and extend service life,” which is quite accurate. On DC charging stations, some components in the high-voltage and drive circuit units have exposed metal pins, making them vulnerable to moisture.